IMPLEMENTATION OF HYBRID FILTER FOR HARMONICS REDUCTION IN NON-LINEAR LOADS
Yahya
Chusna Arif
Politeknik Elektronika
Negeri Surabaya, Indonesia Email: [email protected]
ABSTRACT
|
The efficiency of electrical power can be improved
by improving power quality. Installing
capacitor banks is one way to improve power quality by improving the power
factor. On the other hand,
the use of non-linear loads
is increasing. This load produces a non-sinusoidal waveform
which causes harmonics to appear in the electric
power system. Harmonic problems will become a serious problem in the power system when there is a capacitor bank in the system which will
cause resonance risk at the
harmonic frequencies. This resonance problem can be solved by installing a detuned filter. Detuned
filters can reduce harmonics and protect the
system from the resonance risk. However, the detuned filter
installation is not sufficient to reduce all harmonics that
generated by non-linear loads, so the
system needs to be equipped with an active
filter. In this
study, using a combination of 14% detuned filter and active filter, each
of which is attached parallel to the load. The result of power quality improvement can increase the power
factor from 0.6
to 0.88, THDi is reduced from
49.5% to 18%,
and THDv is reduced from
2.18% to 1.97%
after installing the hybrid filter |
|
|
KEYWORDS |
Detuned filter,
Filter aktif, Hybrid
filter, Harmony, Capacitor bank |
||
INTRODUCTION
The higher the cost / tariff of electricity, the demand for efficiency in the use of electrical power is the main consideration. The efficiency of electrical power consumption can be done by improving the quality of power. Improving the quality of power, one of which is done by improving the power factor. Capacitor banks are one way to do this power efficiency by fixing the power factor or cosphi. Good electrical power quality when cosθ>0.85 value, constant voltage despite variable
loads, constant frequency, sinusoidal waveform, (Sukir & Soenarto, 1993) (Baggini, 2018) (Hendik et al., 2020)
On the other hand, the use of non-linear loads in electric power systems is increasingly massive and these loads produce non-sinusoidal waves. This creates harmony in the electric power system. Harmonia itself is a disturbance that in the distribution of electric power caused by the presence of distortions of current and voltage waves that cause the formation of non-sinusoidal waves at the frequency of spherical multiples of its fundamental frequency, (Efandi et al., 2016) (Das, 2020), The harmonics that appear have many disadvantages, including: damaging electrical equipment, reducing the lifetime of electrical equipment, increasing the temperature of conductors / conducting wires, causing reading errors in analog measuring instruments, decreasing power efficiency, decreasing power factors, resonance between capacitors and transformers that cause over voltage (Cahyoko, 2020). Harmonics in the electric power system can interfere with the performance of equipment and can even damage it, so that it is detrimental to customers as well as to electrical power providers.
The installation of capacitor banks that are actually functioned to increase the power factor in systems that have non-linear loads will be dangerous because it can pose a risk of resonance both series and parallel resonance. This problem can be overcome by equipping capacitor banks with detuned filters. Detuned filters work by shifting the resonant frequency of the system so that it does not occur at harmonic frequencies so that the risk of resonance can be avoided (Aliyya et al., 2020).
On its implementation detuned filter not yet sufficient to reduce the harmonics produced by non-linear loads, so it needs to be supplemented by filter active to eliminate the lingering harmonics. Combination filter passive and filter active on a system commonly referred to as filter Hybrid (Dahlan, 2009; Setiawan et al., 2018; Sung et al., 2000). Detuned filter as filter Passive deep filter Hybrid Serves as protection of capacitor banks from resonance due to the use of non-linear loads and result from the signal filter active, it also serves to increase the value of low power factor. While filter active on filter Hybrid serves to reduce the harmonic still remaining/appears on the system.
There are several topologies of hybrid filters as in Figure 1, namely: active series filter with parallel passive filter, parallel active filter with parallel passive filter, and active filter series with passive filter (Chen & von Jouanne, 2001; Demirdelen et al., 2013; Nair & Sankar, 2015; Srivatsav et al., 2014; Wong et al., 2008).
(c) Series
active filter with passive filter
Hybrid power filters are used as a solution to the shortcomings of active filters and passive filters when each of these filters is used individually, when combined into a hybrid filter. Active filters can solve harmonic problems in dynamic non- linear loads that passive filters cannot overcome. Meanwhile, passive filters are able to overcome the weaknesses of active filters by reducing the need for active filter ratings so that the costs needed to provide and install active filters are not too expensive. Hybrid filters are generally designed to reduce the cost and rating of active filters by combining with detuned filters that function to reduce harmonics at the most dominant harmonic frequencies and supply the reactive power required by the system (Luo et al., 2009).
From the background that has been explained, the implementation of hybrid filters with topologies in parallel as in Gb. 1 (c) which consists of a detuned filter and active filter that is functioned to improve power factor and harmonic reduction so that the existing harmonics are in accordance with the allowable IEEE 519-199 standard 2 (Engineers, 2014).
RESEARCH METHOD
This research took measurement data at the Electric Power System Laboratory at the Surabaya State Electronics Polytechnic Campus. The hybrid filter in this study was shown at Figure 2 with the topology of each filter installed in parallel to the load. In this topology, the detuned filter works by shifting the resonant frequency below the most dominant harmonic frequency and also serves to compensate for the reactive power required by the load so that the power factor
increases. Active filters work by compensating for harmonics that are still left on the system The loads used are inductive linear loads and non-linear loads.
From the data of the n devotees, the initial parameters are obtained as in Table
I. This data is further used for the purposes of calculating capacitor banks and inductors for detuned filters, as well as for determining the capacity of active filters.
TABLE 1 OF SYSTEM MEASUREMENT RESULTS
VLN |
221 V |
VLL |
380 V |
I |
21.58 A |
P |
5.85 KW |
S |
9.5 KVA |
PF |
0,6 |
THDV |
2,18% |
THDi |
49,25% |
A.
Capacitor Bank Planning
A capacitor bank is an electrical equipment that has capacitive properties that function to compensate for inductive properties or is also a set of several capacitors connected in parallel to the load to obtain the capacitive capacity that will be required by the load. The amount of capacitor bank needs in a system canbe calculated through (1) the following (Shwedhi & Sultan, 2020):
Qc = P(tan θ awal
− tan θ
akhir)
(1)
Installation of capacitor banks in a 3-phase system can be done with 2 hubungs, namely the wye (star) circuit and the delta circuit
From the measurement results, a calculation is needed for the magnitude of the capacitor bank needs. From the measurement results, the pf value is 0.6 and will be corrected with a target of 0.9.
cosθ awal = 0,6 → θ = 53,13� cosθ target
= 0,9 → θ = 25,8�
Qc = P(tan
θ awal − tan θ target) Qc = 5,85(tan
53,13 − tan 25,8�)
Qc = 5KVar
Because the system is equipped with a 14 % detuned filter , there will be a shift in the resonant frequency and an increase in voltage in the capacitor. So that the value of the capacitor needs of the bank will also increase.
�� �NC���
QC = (1 −
p)
5
QC = (1 − 0,14)
QC = 5,8KVar
The large capacitance of the capacitor is:
Qc
CY = 2πfV2
5,8
CY = 2
� π � 50 � 3802 CY = 120μF
The capacitor bank in the system is installed with a delta circuit, so the result is as in the following equation:
C��
= CY
∆������������ 3
120
C∆ =��� 3
C∆ = 40μF
From the calculation results above, the amount of delta circuit
capacitor needed for power factor
improvement is as large as 40μF where there are 6
steps of capacitor so that the value is 6.67. μF
C∆ = 6,67μFper step
CY = 20μFper step
B. Detuned Filter Design
In Figure 3 is an algorithm to determine the magnitude of the detuned factor required by the system. The magnitude of the detuned factor (p) and the shift in its resonance frequency can be seen through Table 2.
TABLE 2 DETUNED FACTOR VALUES AND RESONANT FREQUENCY SHIFTS
p |
fres |
5% |
223 Hz |
5,5% |
213 Hz |
5,67% |
210 Hz |
6% |
204 Hz |
7% |
189 Hz |
8% |
177 Hz |
12,5% |
141 Hz |
14% |
134 Hz |
From the results of the initial measurements that have been made, there is a 3rd harmonic in the system. The 14% detuned factor was chosen because what is available on the market is this size, and in this study the large 14% detuned filter is the most suitable to avoid resonance in the 3rd harmonisa (f=150Hz). If you choose a 12.5% detuned filter, the shift in its resonance frequency will be too close to the 3rd harmonic. The resonant frequency of the system with p=14% is shifted to 134 Hz according to the calculation below:
p = (
fn��� 2
)
fres
� 100
fres2
502
= 14 �
100
fres
= √2500 � 100
14
fres = 134Hz
Specifies the magnitude of L for the detuned filter fork each step.
p
L =
14
L = 100 � 4 � π2 � 502 �
20 �
10−6 L
= 70mH
From the results obtained thevalue of L for a 14% detuned filter is 70mH.
C.
Aktif Harmonic Filter for Hybrid
Filter
The way the active filter works is to use power electronics technology that produces specific current components to eliminate harmonic current components due to the use of non-linear loads.
The active power filter on the hybrid filter serves as a current source, compensating for harmonic currents due to the use of non-linear loads. The principle is to inject a compensation current of the same magnitude as the harmonic current, so that the harmonic current is eliminated. The purpose of the active filter is to generate a sinusoidal current with the equation I S=I L-IF. (Arif et al., 2021) If the non-linear load current is the sum of the fundamental current components I Lh and the harmonic current ILF, as in the equation below:
IL = ILf + ILh
Then the compensation current by the active filter will be:
If = ILh
So that the source current is equal to:
IS = IL + If = (ILf + ILh) − ILh
= ILf
The capacity of the active filter in this study was calculated through the following equation:
I = THDi � Iload I
= 49,25%
� 21,58A
I = 10,62A
The active filter in this study has a power capacity of 50A, so it works by injecting 10.62A or about 21% of its total capacity.
RESULT AND DISCUSSION
The real measurement is carried outby combining a 14% detuned filter with an active filter with a capacity of 50A. Based on the results of measurements that have been made, the unfiltered system (hybrid OFF) produces a sinusoidal fixed voltage source but for a current source there is a distortion pat as in Figure.15. THDv and THDi systems are worth 2.18% and 49.25%, respectively. The THDv value is still in accordance with the standard allowed for voltage < 69kV , which must be below 5%, while the THDi value exceeds the standard value allowed by IEEE 519-1992, which exceeds 20%. The power factor value on the unfiltered system is 0.6.
Figure 6 Unfiltered current
harmonic spectrum
.
The measurement results at the time of hybrid filter ON, THDv fell to 1.97% from 2.18% and THDi fell to 18.30% from 49.25% previously.
Figure 8 Harmonic spectrum
current when hybrid filter ON
For more details on the harmonic values of the measurement results can be seen in Table V and Table VI. Meanwhile, the power factor value increased thelevel from the previous one without a filter was 0.6 to 0.88 after the installation of a hybrid detuned filter of 14%.
TABLE 3 COMPARISON OF THD AND POWER FACTORS
|
Hybrid filter
The settings on the active filter are not made maximum due to the limited capacity of the active filter so that the THDi is only reduced to 18.30%. However, this THDi value already meets the standards allowed by IEEE 519-1992 so that it is safe for installation on load and does not interfere with the source.
TABLE 4 COMPARISON OF VOLTAGE HARMONS IN SYSTEMS
Order of the |
Hybrid Filter |
Hybrid
Filter |
Harmonisa |
OFF |
ON |
3 |
0,43% |
0,43% |
5 |
1,18% |
1,08% |
7 |
0,74% |
0,73% |
9 |
0,34% |
0,45% |
11 |
0,88% |
0,78% |
13 |
0,46% |
0,22% |
15 |
0,47% |
0,13% |
17 |
0,84% |
0,85% |
19 |
0,43% |
0,37% |
21 |
0,12% |
0,12% |
23 |
0,03% |
0,08% |
25 |
0,02% |
0,12% |
27 |
0,04% |
0,04% |
29 |
0,05% |
0,03% |
31 |
0,01% |
0,05% |
33 |
0,02% |
0,02% |
35 |
0,01% |
0,04% |
37 |
0,02% |
0,02% |
39 |
0,01% |
0,01% |
41 |
0,02% |
0,02% |
43 |
0,01% |
0,03% |
45 |
0,02% |
0,03% |
47 |
0,01% |
0,01% |
49 |
0,02% |
0,02% |
THDv |
2,18% |
1,97% |
TABLE 5 COMPARISON OF CURRENT HARMONS IN SYSTEMS
Order of harmonics |
Hybrid Filter
OFF |
Hybrid Filter
ON |
3 |
9,04% |
5,14% |
5 |
6,85% |
2,58% |
7 |
2,38% |
1,45% |
9 |
0,49% |
0,34% |
11 |
0,41% |
0,47% |
13 |
0,41% |
0,18% |
15 |
0,59% |
0,20% |
17 |
0,60% |
0,50% |
19 |
0,22% |
0,13% |
21 |
0,28% |
0,14% |
23 |
0,23% |
0,18% |
25 |
0,37% |
0,04% |
27 |
0,12% |
0,03% |
29 |
0,18% |
0,13% |
31 |
0,04% |
0,03% |
33 |
0,03% |
0,03% |
35 |
0,15% |
0,05% |
37 |
0,08% |
0,06% |
39 |
0,06% |
0,01% |
41 |
0,13% |
0,05% |
43 |
0,07% |
0,04% |
45 |
0,05% |
0,01% |
47 |
0,08% |
0,03% |
49 |
0,04% |
0,01% |
THDi |
49,25% |
18,30% |
CONCLUSION
From the results of the study, it was concluded that hybrid filters with an active topology of parallel filters and detuned parallel filters are able to reduce the harmonic value of current and voltage while improving the power factor in the plan system. The power factor increased from the previously unfiltered one was
0.6 up to 0.88 after installing the hybrid filter. In addition, the THDi, which was originally 49.25%, dropped to 18.30% where this value met the IEEE519-1992 standard, which was below 20%. THDv, which was originally 2.18%, fell to 1.98%. The condition meets the IEEE 519-1992 standard of 5% for a voltage of 69 kV
REFERENCES
Aliyya,
J., Arif, Y. C., & Qudsi,
O. A. (2020). Performance Comparison of PI Control and Fuzzy Logic for Speed Control of DC Shunt Motor Using
Matlab/Simulink. JAREE (Journal
on Advanced Research
in Electrical Engineering), 4(2).
Arif, Y. C., Raharja,
L. P. S., & Auladah,
S. (2021). Design
and implementation of hybrid filter
for harmonic reduction and damped resonances in non-linear loads. IOP
Conference Series: Materials Science and Engineering, 1096(1), 12072.
Baggini, A. (2018).
Handbook of power quality. John Wiley
& Sons.
Cahyoko, A. I. (2020). Pengurangan Harmonisa Di Gedung Graha Widya Universitas 17 Agustus 1945 Surabaya. Universitas 17 Agustus 1945 Surabaya.
Chen, L., & von Jouanne, A. (2001). A
comparison and assessment of hybrid filter
topologies and control
algorithms. 2001 IEEE 32nd Annual
Power Electronics Specialists Conference (IEEE Cat. No. 01CH37230), 2, 565�570.
Dahlan, M. (2009). Desain Konfigurasi Paralel Filter Hybrid untuk Meminimalis Ukuran Filter Aktif. Sains dan Teknologi, 2(1).
Das, J. C. (2020). Transients in Electrical Systems, Recognition, Analysis and Mitigation. New York: McG Hill.
Demirdelen, T., Inci, M., Bayindir, K. �., & T�may, M. (2013). Review of hybrid active power filter topologies and controllers. 4th International Conference on Power Engineering, Energy and Electrical Drives, 587�592.
Efandi, R., Pujiantara, M., & Wahyudi, W. (2016). Studi Perencanaan Filter Hybrid Untuk Mengurangi Harmonisa Pada Proyek Pakistan Deep Water Container Port. Jurnal Teknik ITS, 4(2), A142�A147.
Engineers, I. of E. and E. (2014). IEEE recommended practice
and requirements for harmonic
control in electric power systems. IEEE.
Hendik, E. H. S., Yahya, C. A., & Indhana, S. (2020). Teknik Pengurangan Arus Inrush dan Pengurangan Harmonisa Pada Kapasitor Bank Untuk Beban Non Linier. Emitter, 1(1).
Luo, A., Tang, C., Shuai, Z. K., Zhao, W., Rong, F., & Zhou, K. (2009). A novel three-phase hybrid active power filter with a series resonance circuit tuned at the fundamental frequency. IEEE Transactions on Industrial Electronics, 56(7), 2431�2440.
Nair, M. S., & Sankar, D. (2015). A Review of Hybrid filter topologies for power
quality compensation. International
Research Journal of Engineering and Technology
(IRJET), 613�621.
Setiawan, I. W. D., Rinas, I. W., & Weking, A. I. (2018). Analisa Pemasangan Filter Hybrid Terhadap beban-Beban Non Linier Pada Blue Point Bay Villa dan Spa. E-Journal SPEKTRUM Vol, 5, 109�115.
Shwedhi, M. H., & Sultan, M. R. (2020). Power
factor correction capacitors; essentials
and cautions. 2000 Power Engineering Society
Summer Meeting (Cat. No. 00CH37134), 3, 1317�1322.
Srivatsav, C. N., Agarwal, P., & Avinash, C. V. (2014). Types of Hybrid Power Filter and their comparative performance analysis with distorted source
voltage using MATLAB. 2014 International Conference on Advances in Energy Conversion
Technologies (ICAECT), 136�139.
Sukir, S., & Soenarto, S. (1993). Bahaya Nuklir Pltn terhadap Lingkungan: suatu Antisipasi Pencegahan. Cakrawala Pendidikan, 86918.
Sung, J.-H., Park, S., & Nam, K. (2000). New hybrid parallel
active filter configuration minimising
active filter size. IEE Proceedings-Electric Power Applications, 147(2), 93�98.
Wong, M.-C., Lam, C.-S.,
& Dai, N.-Y. (2008). Comparison of structure topologies for hybrid filters. 2008
43rd International Universities Power Engineering Conference, 1�5.